BS03 Fixed Gas Detection Used To Detect Multi Gas
BS03 is fixed a gas detection, it is easy io detect the surrounding gas. It is a multi gas detection, you can use it to detect many different gases in the industrial environment.
Email:
info@hn-guangqun.com
Phone:
+86-13838155309
Detailed Product Description
Fixed Gas Detector Description
BS03 is a fixed gas detector installed in a place where potential gas hazard exists to measure oxygen, toxic gas and combustible gas. It shows not only the concentration of gas but also diagnostic result of the unit itself through the LED screen and LED lights and can be connected to the control panel with a standard 4-20mA analog output.
BS03 is a fixed gas detector installed in a place where potential gas hazard exists to measure oxygen, toxic gas and combustible gas. It shows not only the concentration of gas but also diagnostic result of the unit itself through the LED screen and LED lights and can be connected to the control panel with a standard 4-20mA analog output.
It is applicable to explosion-proof places: Steelworks, Petrochemical plants, Shipyards, Watertreatment plants, Mines, Power plants, Food industry etc.
Fixed Gas Detector Key features
- Interchangeable smart sensor module
- Intrinsically safe
- Built-in sampling pump (optional)
- Visual, audible and vibration alarm
- Adjustable alarm levels and span calibration values
- Password management
- Self-test after power on
- Self-diagnostic and self-correction function
- Real-time clock
Specifications
Measuring gas | Combustible | Catalytic sensor/ NDlR sensor |
Toxic gas & O2 | Electrochemical sensor | |
CO2 gas | NDlR sensor | |
VOCs | PID sensor | |
Measuring range | Refer to our gas list | |
Measuring accuracy | +5%F.S. | |
Sensor life | Catalytic sensor: 3 years Electrochemical: 2 years (1 year for O2 sensor) NDlR sensor: 5 years PiD sensor: 0.6 to 1 year | |
Measuring type | Diffuse naturally | |
Signal output | 4-20mA | |
Alarm output signal | 2 programmable relays | |
Cable / distance | 1.5 MM2 , 3wire, shielded, 1000m (maximum) | |
Conduit connection | G3/4 | |
Response time | Catalytic sensor: T90≤30s Electrochemical: T90≤60s NDlR sensor: T90≤10s PlD sensor: T90≤10s | |
Mounting type | Wall mounted | |
Working temperature | Toxic gas: -20°C~50°C Combustible: -40°C~70°C | |
Working humidity | ≤95%RH(no condensation) | |
Operation voltage | DC24V+25% | |
Consumption | <2W | |
Ingress Protection | IP65 | |
Housing material | Chamber: Aluminum alloy Sensor cover: Stainless steel | |
Dimension and weight | 162mm×208mm×103.5mm, about 2.1kg | |
Approval | Ex II 2G Ex db IIC T6 Gb |