TC100N Fixed Gas Detector To Gas Leak
TC100N is a leak detector, it is also a fixed gas detector, it is easy to detect the surrounding gas like flammable gas, so it is a flammable gas detector.
          
          Email:
          info@hn-guangqun.com
          
          Phone:
          +86-13838155309
        
Detailed Product Description
Fixed Gas Detector Specifications
| Measuring gas | O2 | CO | H2S | Combustible | 
| Measuring range | 0-25%vol | 0-500ppm | 0-100ppm | 0-100%LEL | 
| Resolution | 0.1%vol | 1ppm | 1ppm | 1%LEL | 
| Sensor type | Electrochemical | Electrochemical | Electrochemical | Catalytic | 
| Sensor life | 1 year | 2 years | 2 years | 2 years | 
| Sampling method | Natural diffusion | |||
| Response time | Toxic gas and O2: T90≤60s; Combustible: T90≤30s  | |||
| Working temperature | -20℃~50℃ for toxic gas -40℃~70℃ for combustible gas  | |||
| Signal output | 4-20mA/RS485 | |||
| Alarm output signal | 2 programmable relays for 4~20mA type | |||
| Conduit connection | G1/2 | |||
| Cable required | ≥1.5mm2×3 core cable(4-20mA type) ≥1.5mm2×4 core cable(RS 485 type)  | |||
| Transmission distance | ≤1000m | |||
| Mounting type | Wall mounted | |||
| Working temperature | oxic gas:-20℃~50'C Combustible gas: -40℃~70℃  | |||
| Working humidity | ≤95%RH(no condensation) | |||
| Operation voltage | DC24V±25% | |||
| Consumption | <2W | |||
| Ingress Protection | IP65 | |||
| Housing material | Chamber: Aluminum alloy Sensor cover: Stainless steel  | |||
| Dimension and weight | 196mm×186mm×68.5mm, about 1.2kg | |||
| Approval | Ex Ⅱ 2G  Ex db llC T6 Gb | |||
| Cable / distance | 4-20mA type: 1.5 MM2, 3 wire, shielded,1000m (maximum) RS485 type: 1.5 MM2, 4 wire, shielded, 1000m (maximum)  | |||
Fixed Gas Detector Key features
- ATEX approved
 - 4-20mA analog or RS485 digital output
 - 2 relay output for 4-20mA type
 - Sensor module design, easy for replacement
 